Unit-of-Measure Equivalents
| Unit | Equivalent |
| Kilowatt (kW) | 1,000 Watts |
| Megawatt (MW) | 1,000,000 Watts |
| Gigawatt (GW) | 1,000,000 Kilowatts (kW)=1,000,000,000 Watts |
| Kilowatt-hours (kWh) | 1,000 Watt-hours |
| Megawatt-hours (MWh) | 1,000,000 Watt-hours |
| Gigawatt-hours (GWh) | 1,000,000,000 Watt-hours |
| U.S.Dollar | 1,000 Mills |
| U.S.Cent | 10 Mills |
| Btu (British Thermal Unit) | 252 Calories |
Conversions / Calculations
Annual kWh of Generation Calculated from kW Capacity:
kW * Capacity Factor * Annual Hours = Kilowatt-hours
Annual kWh of Consumption Calculated from kW Load Factor:
kW * Load Factor * Annual Hours = Kilowatt-hours
kVa to kW Conversion:
Heat Rate:
Heat Rate = Btu (heat input) per kWh (electricity output)
Dollars ($) per Btu to Dollars ($) per kWh:
$ / kWh = Heat Rate * $ / Btu
Hourly Demands (kW) from 15-minute (kWh) Interval Data:
For estimated hourly demand, multiply the kWh value for the time period by 4
(i.e., Estimated kW = kWht * 4)
For actual demand for the hour, add the four consecutive 15 time periods (i.e.,
Actual kW = kWh1 + kWh2 + kWh3 + kWh4)
For peak demand for the hour, multiply the largest of the four consecutive 15
time periods by 4 (i.e., Peak Demand (kW) = kWhLargest * 4)
Load Factor (%):
kWh /(kW * hours) for a time period
Average Fuel Conversion Factors
| Electricity: | 3,412 Btu/kWh |
| Fuel Oil: | 138,700 Btu/gallon |
| Natural Gas: | 1,030 Btu/cubic foot |
| LPG/Propane: | 95,500 Btu/gallon |
| Coal: | 24,580,000 Btu/ton |
| Purchased Steam: | 1,000 Btu/pound |
|